Experimental investigation of the delamination behavior of curved post-tensioned concrete structures without through-thickness reinforcement

dc.contributor.advisorHrynyk, Trevor
dc.contributor.advisorBayrak, Oguzhan, 1969-
dc.creatorWoods, Clint Robert
dc.creator.orcid0000-0001-6927-2926
dc.date.accessioned2019-01-25T23:22:54Z
dc.date.available2019-01-25T23:22:54Z
dc.date.created2016-12
dc.date.issued2016-10-03
dc.date.submittedDecember 2016
dc.date.updated2019-01-25T23:22:54Z
dc.description.abstractThe recent delamination failure of the concrete containment structure wall at the Crystal River Unit 3 Nuclear Power Plant has led to increased interest in the mechanical behavior of curved post-tensioned structures. Extensive investigations have been performed to identify the causes of the delamination failure, but no experimental research has focused on the behavior of curved post-tensioned structures. Analytical studies focused on the through-thickness stress development stemming from prestressing forces have been performed, yet there is no experimental data to verify the results. This research examines the behavior of curved post-tensioned structures and their delamination failures through the structural testing of two curved post-tensioned wall specimens. Two 90° curved post-tensioned wall specimens were constructed and tested under monotonically increasing prestressing loads at the University of Texas at Austin. In an effort to gain insight into the size effect associated with delamination failures, the dimensions of the second specimen were doubled from the first. The specimens were well-instrumented to ensure the delamination behavior was adequately captured. Using the output from load cells positioned at the live-end and dead-end of each curved wall specimen, the friction losses, forces, and stresses developed at various locations along the curved wall sections were determined. In order to directly compare the behavior of both specimens, the applied stresses were normalized with respect to the measured concrete compressive strength. The test results were used to determine the underlying mechanisms of the curved post-tensioned concrete structures, such as the size effect of delamination failure and initiation of delamination cracking. The experimental results indicated an apparent size effect on the delamination resistances of the curved wall specimens, with a 32 % decrease in the normalized capacity from Specimen 1 to Specimen 2. In addition, the compressive stresses at the initiation of the delamination crack were 0.13f [subscript c]’ ~ 0.23f [subscript c]’, which are significantly less than the allowable stress limit of 0.35fc’ specified in ASME Boiler and Pressure Vessel Code (BPVC) Section III, Division 2 for the service load condition. Lastly, the measured friction losses were 38%~43% greater than the friction losses calculated based on ACI 343R-95.
dc.description.departmentCivil, Architectural, and Environmental Engineering
dc.format.mimetypeapplication/pdf
dc.identifierdoi:10.15781/T2MK65V8X
dc.identifier.urihttp://hdl.handle.net/2152/72468
dc.language.isoen
dc.subjectDelamination
dc.subjectDelamination failure
dc.subjectDelamination crack
dc.subjectNuclear containment
dc.subjectCurved post-tensioned concrete structure
dc.subjectFriction loss
dc.titleExperimental investigation of the delamination behavior of curved post-tensioned concrete structures without through-thickness reinforcement
dc.typeThesis
dc.type.materialtext
thesis.degree.departmentCivil, Architectural, and Environmental Engineering
thesis.degree.disciplineCivil Engineering
thesis.degree.grantorThe University of Texas at Austin
thesis.degree.levelMasters
thesis.degree.nameMaster of Science in Engineering

Access full-text files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
WOODS-THESIS-2016.pdf
Size:
10.02 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
LICENSE.txt
Size:
1.84 KB
Format:
Plain Text
Description: